5604-RIO-PDPMV1

5604-RIO-PDPMV1

Limited Availability

The ProLinx® family Allen Bradley Remote I/O Adapter to PROFIBUS DPV1 Master communications module (5604-RIO-PDPMV1) creates a powerful connection between devices on a Remote I/O network and PROFIBUS slave devices. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Remote I/O port and a PROFIBUS DPV1 Master with a RS-485 9-pin D shell female connector interface with isolated Opto-Couplers.

The RIO interface is an adapter (slave) which can be connected to a RIO scanner (master) that controls the data transfer.

  • Description

Description

Rockwell Automation Remote I/O to PROFIBUS DPV1 Master Gateway

5604-RIO-PDPMV1

Profibus to A B Remote

The ProLinx® family Allen Bradley Remote I/O Adapter to PROFIBUS DPV1 Master communications module (5604-RIO-PDPMV1) creates a powerful connection between devices on a Remote I/O network and PROFIBUS slave devices. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Remote I/O port and a PROFIBUS DPV1 Master with a RS-485 9-pin D shell female connector interface with isolated Opto-Couplers.

The RIO interface is an adapter (slave) which can be connected to a RIO scanner (master) that controls the data transfer.

The PROFIBUS DPV1 Master (PDPMV1) protocol driver supports Master implementations of the protocol on either a Mono-Master or Multi-Master network. The DPV1 master supports FDT/DTM communication when using the PSW-cDTM-PDPM FDT communication DTM. The PROFIBUS DPV1 Master FDT communication DTM software is an interface between any compliant FDT software container, an FDT device DTM and applicable PROFIBUS slave devices.

The ProLinx Communication Modules provide connectivity for two or more dissimilar network types. The modules, encased in sturdy extruded aluminum, are stand-alone DIN-rail mounted protocol gateways, providing communication between many of the most widely used protocols in the industrial automation today.

 

Features and Benefits

Applications

Allows for legacy Allen-Bradley 1771 PLC5 controllers with native Remote I/O communication ports to act as PROFIBUS DPV1 Masters on a PROFIBUS network.

 

Specifications

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

 

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

 

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

 

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

 

 