Modbus TCP/IP to Siemens Industrial Ethernet Communication Gateway
PLX32-MBTCP-SIE
ProSoft Technology’s Modbus® TCP/IP to Siemens Industrial Ethernet gateway allows high speed bi-directional data transfers between Schneider Electric® PACs and Siemens S7 and S5 PACs.
Two ports allow each protocol to reside on separate subnets, allowing you to pass data between the two subnets without changing each device’s IP address.
- Description
Description
Modbus TCP/IP to Siemens Industrial Ethernet Communication Gateway
ProSoft Technology’s Modbus® TCP/IP to Siemens Industrial Ethernet gateway allows high speed bi-directional data transfers between Schneider Electric® PACs and Siemens S7 and S5 PACs.
Two ports allow each protocol to reside on separate subnets, allowing you to pass data between the two subnets without changing each device’s IP address.
Architectures
Features and Benefits
- Two separate Ethernet ports allow each protocol to reside on separate subnets. This allows you to pass data between the two subnets without changing each device’s IP address to be on the same subnet.
- In addition to S7 controllers, the gateway can also be used with Siemens S5 controllers with an appropriate interface.
- Gateway includes a SD card slot (SD card optional) for storing configuration files. This can be used for disaster recovery.
- Secure module configuration via module switch (v1.04 and greater).
- Up to 10,000 16-bit registers can be used to exchange large amounts of data
Specifications
Modbus TCP/IP Specifications
Specification | Description |
Supported Modbus Function Codes | 1: Read Coil Status 2: Read Input Status 3: Read Holding Registers 4: Read Input Registers 5: Force (Write) Single Coil 6: Preset (Write) Single Holding Register 15: Force (Write) Multiple Coils 16: Preset (Write) Multiple Holding Registers 22: Mask Write Holding Register (Slave Only) 23: Read/Write Holding Registers (Slave Only) |
Supported Clients | 10 |
Supported Servers | MBAP: 5 Encapsulated: 5 |
Command List | Up to 160 fully configurable Client commands |
Status Data | Error codes reported individually for each command |
Command List Polling | Each command can be individually enabled or disabled; write-only-on-data-change is available |
Siemens Industrial Ethernet Specifications
Specification | Description |
Supported PLC Data Exchange (Read and Write) | Siemens S7-200, S7-300, S7-400, S7-1200, S7-1500 |
Supported Register Types | DB, Inputs, Outputs, Flags, Counters, Timers |
Supported Clients | 20 |